山東電纜橋架:電纜溝防火隔板設(shè)置要求
電纜溝防火隔板設(shè)置要求
Requirements for setting fire barriers in cable trenches
電纜溝防火隔板的設(shè)置要求主要包括以下幾點(diǎn):
The requirements for setting up fire barriers in cable trenches mainly include the following points:
防火隔板的適用場所:防火隔板主要適用于各類電壓等級的電纜在支架或橋架上敷設(shè)時(shí)的防火保護(hù)和耐火分隔,大量應(yīng)用在發(fā)電廠、化工企業(yè)、鋼鐵冶煉企業(yè)、礦山等電纜密集場所的電纜工程。
Applicable places for fire barriers: Fire barriers are mainly used for fire protection and fire-resistant separation of cables of various voltage levels when laid on brackets or bridges. They are widely used in cable engineering in cable intensive places such as power plants, chemical enterprises, steel smelting enterprises, and mines.
隔板設(shè)置間距:對于阻燃電纜,在電纜溝每隔80~100m處設(shè)置一個(gè)隔斷;對于非阻燃電纜,宜每隔60m設(shè)置一個(gè)隔斷。一般設(shè)置在臨近電纜溝交叉處。
Partition spacing: For flame-retardant cables, a partition should be set every 80-100m in the cable trench; For non flame retardant cables, it is advisable to set up partitions every 60m. It is generally set near the intersection of cable trenches.
安裝方式:防火墻的安裝方式為兩側(cè)采用標(biāo)準(zhǔn)厚度的防火隔板封隔、中間采用無機(jī)堵料、防火包或耐火磚堆砌,其厚度根據(jù)產(chǎn)品的性能而定,一般不小于250mm。
Installation method: The installation method of the firewall is to use standard thickness fireproof partitions on both sides, inorganic blocking materials, fireproof bags or refractory bricks in the middle, and the thickness depends on the performance of the product, generally not less than 250mm.
電纜包裹要求:防火墻內(nèi)的電纜周圍必須采用不得小于20mm的有機(jī)堵料進(jìn)行包裹。
Cable wrapping requirements: The cables inside the firewall must be wrapped with organic blocking material not less than 20mm around them.
排水孔洞:防火墻頂部用無機(jī)防火堵料填平整,并加蓋防火隔板,底部必須留有兩個(gè)排水孔洞,排水孔洞處可利用磚塊砌筑。

Drainage holes: Fill the top of the firewall with inorganic fireproof blocking material and cover it with fireproof partitions. Two drainage holes must be left at the bottom, and bricks can be used to build the drainage holes.
其他要求:防火隔板應(yīng)存放在通風(fēng)干燥處,避免雨淋,運(yùn)輸時(shí)應(yīng)防止雨淋,搬運(yùn)時(shí)應(yīng)避免損壞。
Other requirements: Fire barriers should be stored in a ventilated and dry place to avoid rain, and should be protected from rain during transportation. Damage should be avoided during handling.
以上是電纜溝防火隔板的設(shè)置要求,具體設(shè)置還需根據(jù)實(shí)際情況和相關(guān)規(guī)范進(jìn)行調(diào)整。
The above are the requirements for setting fire barriers in cable trenches, and the specific setting needs to be adjusted according to the actual situation and relevant specifications.
以上就是有關(guān):山東電纜橋架 的介紹,想了解更多的內(nèi)容請點(diǎn)擊:http://www.qianhe02.com 我們將會全心全意為您提供滿分服務(wù),歡迎您的來電!
The above is an introduction to Shandong cable tray. For more information, please click: http://www.qianhe02.com We will wholeheartedly provide you with full score service. Welcome to call us!
下一篇:濟(jì)南電纜橋架:電纜橋架的發(fā)展史
相關(guān)文章 / Recommended news
- 山東電纜橋架屋頂?shù)跹b:配件清單+標(biāo)準(zhǔn)化流程,新手也能零失誤
- 濟(jì)南電纜橋架安裝:200多斤600×200橋架,這樣吊裝又
- 山東電纜橋架定制:耐火板與防火型的核心區(qū)別,一文讀懂避坑指南
- 濟(jì)南電纜橋架選型誤區(qū):100×100規(guī)格加隔板難?航豐的方案破解施工難題
- 山東電纜橋架避坑!貫穿孔成火災(zāi)“隱形通道”?3步防火實(shí)操筑牢防線
- 濟(jì)南電纜橋架鋪設(shè)踩坑,層數(shù)、根數(shù)、限制,規(guī)范不看必返工
- 山東電纜橋架(鍍鋅款)接地線誤區(qū),接錯(cuò)必返工,規(guī)范要點(diǎn)一文說清
- 濟(jì)南電纜橋架線纜捆扎錯(cuò)了=埋隱患,4種規(guī)范方法,施工必看
- 山東不銹鋼橋架現(xiàn)場打孔避坑!4步標(biāo)準(zhǔn)流程,90%施工方少走彎路不損橋架
- 山東電纜橋架選型封神指南!記住3句話,70%工程方避開選型陷阱不花冤枉錢
陽極氧化鋁合金橋架
托盤式電纜橋架
梯式電纜橋架
梯式不銹鋼電纜橋架
深灰色金屬防火電纜橋架